Observability and Criticality Analyses for Power Systems Measured by Phasor Measurements


Goel M. , Abur A.

IEEE TRANSACTIONS ON POWER SYSTEMS, cilt.28, ss.3319-3326, 2013 (SCI İndekslerine Giren Dergi) identifier identifier

  • Cilt numarası: 28 Konu: 3
  • Basım Tarihi: 2013
  • Doi Numarası: 10.1109/tpwrs.2012.2236367
  • Dergi Adı: IEEE TRANSACTIONS ON POWER SYSTEMS
  • Sayfa Sayıları: ss.3319-3326

Özet

This paper proposes observability and measurement criticality analysis methods for any type of current phasor measurement configurations. Measurement Jacobian cannot be decoupled when using current phasor measurements and thus conventional methods of network observability analysis can no longer be used. Current phasor measurements may be classified into two types based on their configuration. Depending on whether there is a voltage phasor measurement at the sending end of the measured line or not, a current phasor measurement configuration may be referred to as of type-1 or type-2, respectively. Two methods which can handle conventional as well as phasor measurements, one being a modified version of the conventional method for type-1, and the other being a new method for type-2 phasor measurements, are developed and presented. Moreover, due to the fully coupled model used in the analysis, a method to handle voltage magnitude measurements is also developed.