Impact of DFIG impedance model precision on stability analysis


Xue T., Karaagac U., Ghafouri M.

ENERGY REPORTS, cilt.9, ss.920-929, 2023 (SCI-Expanded, Scopus) identifier identifier

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 9
  • Basım Tarihi: 2023
  • Doi Numarası: 10.1016/j.egyr.2023.05.165
  • Dergi Adı: ENERGY REPORTS
  • Derginin Tarandığı İndeksler: Science Citation Index Expanded (SCI-EXPANDED), Scopus, Compendex, INSPEC, Directory of Open Access Journals
  • Sayfa Sayıları: ss.920-929
  • Orta Doğu Teknik Üniversitesi Adresli: Hayır

Özet

Impedance-based stability analysis (IBSA) is an effective method to analyze the interaction problem between the doubly-fed induction generator-based wind park (DFIG-WP) and series compensated or weakly tied AC grids. The analytical impedance model of DFIG has evolved over the years for better precision. This paper presents a precision comparison of those analytical models where the reference is obtained through EMT-level frequency scanning simulations. Moreover, representative IBSA is also performed with those models on typical test systems in which the DFIG adversely interacts with the series compensated grid and weakly tied AC grid in sub- and super-synchronous frequency ranges, respectively. The common modeling approach, which disregards the coupling between the rotor side converter (RSC) and grid side converter (GSC) at the DC-side, reduces the accuracy of IBSA and may lead to incorrect stability analysis results. (c) 2023 The Author(s). Published by Elsevier Ltd. This is an open access article under the CCBY license (http://creativecommons.org/licenses/by/4.0/).