A New Field-Data Based EAF Model for Power Quality Studies


Goel M., Salor O., Alboyaci B., Mutluer B., Cadirci I., ERMİŞ M.

IEEE Industry-Applications-Society Annual Meeting, Alberta, Kanada, 5 - 09 Ekim 2008, ss.21-22 identifier identifier

  • Yayın Türü: Bildiri / Tam Metin Bildiri
  • Doi Numarası: 10.1109/08ias.2008.335
  • Basıldığı Şehir: Alberta
  • Basıldığı Ülke: Kanada
  • Sayfa Sayıları: ss.21-22
  • Orta Doğu Teknik Üniversitesi Adresli: Evet

Özet

A new electric arc furnace (EAF)-specific model based on field measurements of instantaneous furnace voltages and currents has been proposed. This model presents the dynamic behavior of the EAF system including all parts, i.e. the EAF transformer, the secondary circuit, the electrode movements and the arc. It consists of a cascade connected variable-resistance and -inductance combination to represent the time variation at the fundamental frequency, and a current source in parallel with it to inject the harmonics and interharmonics of the EAF current. The model takes into account several typical tap-to-tap periods of the specific EAF operation. This model is especially advantageous for power quality (PQ) analysis, and development of FACTS solutions for PQ problem mitigation of a given busbar supplying single- or multi-EAF installations. The validity of the proposed model has been verified by comparing EMTDC/PSCAD simulations of the model with the field measurements. The results obtained have shown quite satisfactory correlation between the proposed model and the actual EAF operation.