Özet:

Voltage fluctuations under 30 Hz in the electricity grid, leads to oscillations in the light intensity that can be perceived by human eye, which is called flicker. In this thesis, the sources of the flicker at a point of common coupling is investigated. When there are more than one flicker sources connected to a PCC, individual effects of each flicker source is determined by using a new method which depends on the reactive current components of the sources. This method is mainly based on the flickermeter design defined by the International Electrotechnical Commission (IEC), but uses the current variations in addition to the voltage variations to compute flicker. The proposed method is applied to several different types of loads supplied from a PCC and their flicker contributions on the busbar are investigated. Experiments are performed on field data obtained by the power quality analyzers (PQ+) developed by the National Power Quality Project and the method has been found to provide accurate results for flicker contributions of various loads. The PQ+ analyzers with the proposed flicker contribution detection algorithm are called Flicker Contribution Meters (FCM) and they will be installed at the points of the Turkish Electricity Transmission Network when required.